Simpson Electric H340 User Manual

Hawk 3-Temperature  
H340  
4 Digit  
Advanced Digital Controller  
OPERATORS MANUAL  
SIMPSON ELECTRIC COMPANY 520 Simpson Avenue  
Lac du Flambeau, WI 54538-0099 (715) 588-3311 FAX (715) 588-3326  
Printed in U.S.A. Part No. 06-117489 Edition 5, 06/07  
NOTES:  
NOTES  
22  
3
20mA) When the display reaches 0 percent the analog output would be 4mA.  
Contents  
The limits can be moved or reversed (HI=0 and LO= 80.0), in this case when  
the display reads 0 , the analog output would be 20mA and when the display  
reads 80, the analog output would be 4mA.  
1. INTRODUCTION .............................................................................. 5  
1.1 General Description .............................................................................. 5  
1.2. Specifications........................................................................................ 5  
2. DISPLAY AND KEYPAD CONTROLS............................................... 6  
3. INSTALLATION AND PANEL CUTOUT ............................................. 6  
3.1 Mounting Requirements ....................................................................... 6  
3.2 Engineering Label Placement .............................................................. 7  
4. REMOVING / INSTALLING OPTION MODULES .............................. 7  
5. OPERATING THE KEYS................................................................... 8  
5.1 In Run Mode ......................................................................................... 8  
5.2 In Program Mode .................................................................................. 8  
5.3 In Edit Mode.......................................................................................... 8  
6. PROGRAMMING MENU................................................................... 9  
6.1 Relay Control ........................................................................................ 9  
6.2 Display Control ...................................................................................10  
6.3 Measurement Control ......................................................................... 10  
6.4 Output Control (If Present).................................................................. 11  
6.5 System Control ...................................................................................11  
6.6 Password ............................................................................................ 12  
7. TEMPERATURE INPUT CARDS .................................................... 13  
7.1 Relay Cards ........................................................................................ 13  
7.2 Frequently Asked Questions ............................................................... 14  
7.3 Power Supply Card ............................................................................. 14  
8. MENU FLOWCHART ...................................................................... 16  
9. MENU DETAIL ................................................................................ 18  
The Fail Safe option (FS) controls the action of the analog output when the  
display goes into over-range (EEEE or –EEEE). In some cases, the low limit  
or high limit are reserved for error conditions. With set to ‘HI’, the output will  
run to the 20mA value when over-range or under-range occur. With failsafe set  
to ‘LO’, the output will run to 4mA at over-range or under-range. With failsafe  
‘Off’, the output will go to the defined limit ends. (-EEEE would be 4mA and  
EEEE would be 20mA typically.)  
9.1 Relay Control (Sp1-Sp4)..................................................................... 18  
9.1.1 Response .............................................................................................. 18  
9.1.2 Delay ..................................................................................................... 18  
9.1.3 Latch ..................................................................................................... 19  
9.1.4 Alarm ..................................................................................................... 19  
9.2 Display Control ...................................................................................19  
9.3 Output Control .................................................................................... 20  
4
21  
The display banding, band, works from a different approach. The value en-  
tered is the amount of digit movement allowed before the display should be  
updated. With a band setting of 2, the value must move 2 counts up or down in  
the rightmost position as compared to the current display to cause the display  
to update.  
1.  
INTRODUCTION  
1.1  
General Description  
The Simpson Electric Hawk 3 Advanced Digital Panel Meter/Controller has 4-  
digit display. All LEDs are 7 segment and offer 5 brightness levels. The high  
quality instrument has user programmable parameters that are all set from the  
front panel in easy to understand terminology. The display also shows acti-  
vated set point indicators (up to four). The keypad buttons have audible and  
tactile feedback to prevent keystroke errors.  
NOTE: The two previous features can finely or coarsely stabilize the display  
and remove the pops and jitters typically found when monitoring a power line.  
The adjustment of this setting only filters what is displayed. The actual raw  
signal is evaluated against the setpoint and will go into alarm even if the  
display were set for maximum filtering and gave no indication of nearing the  
setpoint. Use hysteresis on delay in SP menu to slow relay action.  
1.2. Specifications  
The Brit( Brightness) of the display is adjustable to allow for dimming in low  
light applications or for intensity matching with other equipment. The default is  
set to the brightest setting (5).  
Specifications  
Display:  
Type:  
Quantity:  
Height:  
7-segment, red LED  
4
ICE (Zero or Null) Using ICE allows the user to grab a running offset and zero  
to it. A running offset can be useful for monitoring the tolerance to a value  
instead of the value, cancelling lead error in measurement or removing some  
signal difference in a measurement. Once ICE in enabled in the menu (ICE =  
ON), the device will wait until the user presses S and T . At that point, the unit  
will grab the current value and offset the display to zero. By choosing “hold” in  
the ICE menu the ICE value can then be saved to a more permanent location.  
No new ICE can be be taken, but the value will noy be lost if power fails.  
0.56” (14.2mm)  
Decimal Point:  
None  
Non Programmable  
Brightness:  
5 settings  
User Programmable  
Over-range:  
Under-range:  
Alarm Indicators  
Sensor Break:  
(Burnout)  
Display Reads EEEE Indicating Maximum Value  
Display Reads -EEEE Indicating Minimum Value  
4 LED indicators For up to 4 Independent Setpoints  
Display reads EEEE  
NOTE: Be aware that introducing a ICE value will change the setpoint thresh-  
olds and erase any previous Hi Lo readings.  
Power Requirements:  
AC Voltages:  
DC Voltages:  
HILO (Min/Max) allows the user track the history of the readings on the dis-  
play. By pressing S, the unit will momentarily display the highest value it has  
reached after last being reset. By pressing T, the unit will momentarily display  
the lowest value it has reached after last being reset.  
85 to 250 VAC/120 VAC @ 7W  
9 to 36V DC @ 10W  
Accuracy:  
All measurements are at 25° C and measured as  
percent of reading.  
9.3  
Output Control  
Unit Type  
RTD PT100  
Accuracy  
.2%. +/- 2 Count  
Temperature Range  
-200ЊC to +200ЊC  
-100ЊC to +760ЊC  
-200ЊC to +1250ЊC  
-100ЊC to +800ЊC  
-200ЊC to +400ЊC  
An optional analog outputs is available.  
J
K
E
T
.2%. +/- 2 Count  
.2%. +/- 2 Count  
.2%. +/- 2 Count  
.2%. +/- 2 Count  
The analog output is a current or voltage that represents an equivalent range  
of signal on the input. Analog output can be purchased as 4-20mA DC out or  
0-10V DC out. When installed, the Hawk 3 will sense the card and the menu  
will open the choices available to it.  
Environmental  
Operating Temperature.  
Storage Temperature.  
Relative Humidity:  
Ambient Temperature:  
Temperature Drift:  
Warm up Time:  
0 to 50°C  
-10 to 60°C  
<85%  
Setting the limits (LIM). The ends of the analog output range (4 & 20 or 0 & 10)  
can be set or ‘pegged’ to and display value within the range of the meter.  
25°C  
Example: The Hawk 3 is purchased as a standard 200 volt meter. The analog  
output is configured, by default, for HI=100.0 and LO=0.  
When the display reaches 100 volts, the analog output would be 20mA. When  
the display reaches 0 volts the analog output would be 4mA.  
The Hawk3 is purchased as a process meter 4 – 20 mA input which will dis-  
play 0-100 percent. The analog output is configured, by default, for HI=100.0  
and LO=0. This means when the display reached 100 percent the analog out-  
put would be 20 mA. (Also, because this is a process meter the input should be  
Ϯ100 ppm/C°Ϯ0.05dgt/ЊC  
10 minutes  
Noise Rejection  
NMRR:  
CMRR:  
60dB @ 50/60 Hz  
100 db @ 50/60 Hz  
A to D Conversion  
Technique:  
Sample Rate:  
Display Rate:  
Successive Approximation with oversampling  
10 Conversions per second  
User Programmable from 1/minute - 8/second  
20  
5
seconds the alarm will trip and remain in alarm until the display drops below  
the setpoint for at least 2.5 seconds  
2.  
DISPLAY AND KEYPAD CONTROLS  
9.1.3 Latch  
When choosing Ltch, the relay output will latch immediately after crossing the  
setpoint. The unit can then only be unlatched with a front panel reset or a reset  
command from the RS-485 port.  
NOTE: If the display is still beyond the setpoint threshold, the reset will have  
no effect and the unit will remain latched.  
1. Activated set point indicators (4)  
2. 4-button Keypad  
3. Units Window  
9.1.4 Alarm  
4. Numeric and message  
The Alr mode allows choice between High, Low, or Off. The High Alarm means  
that the display value must be greater or equal to the setpoint to go into Alarm.  
The Low Alarm means that the display value must be less than or equal to the  
setpoint to into alarm The Off Alarm means that all features of this setpoint is  
disabled. No action will occur when display crosses a setpoint and the relays  
will revert to a normally de-energized state.  
Figure 2-1  
When selecting St (State) from the menu, the display will alternate between  
3.  
INSTALLATION AND PANEL CUTOUT  
Stand the current setting.  
RESET  
ENTER  
To edit the setting press . Otherwise press T to move to the next choice.  
1.77"  
45mm  
3.56  
90.7mm  
If choosing ND (Normally De-energized) the relay will turn “on” the alarm con-  
dition. This is a typical configuration. The one and two-relay outputs will act as  
abeled; the normally closed contact will be closed until an alarm condition  
occurs, and the opposite is true for the normally open connection. The four-  
relay output only has the choice of normally open.  
3.62"  
92mm  
If choosing NE (Normally Energized) the relay will turn on at power up and  
remain on until in an alarm condition. This mode can be used to create a fail-  
safe condition or reverse the action of the four-relay configuration. In the fail-  
safe example, the relay output would be wired to protect some device during  
an alarm condition. During a power failure, the relay would be in the same  
position as though it were in alarm thus protecting a device that may be on a  
separate and possible active circuit.  
0.52"  
13.2mm  
3.93"  
99.8mm  
3.24"  
82.3mm  
1.76"  
44.7mm  
2.04"  
51.8mm  
Engineering Label  
9.2  
Display Control  
The next item that will appear in the menu is Dctl (Display Control). If this is  
RESET  
Figure 4-1. Installation and Panel Cutout  
the item to be edited press  
to the next choice.  
, otherwise press the down arrow T to move  
ENTER  
The display degrees, Deg, will allow you to select either °F or °C for the tem-  
perature indication. There is no need to change this value if you prefer the  
default °C indication.  
3.1  
Mounting Requirements  
The Hawk 3 Advanced Digital Controller 1/8 DIN counters require a panel  
cutout of 1.77” (45mm) high be 3.62” (92mm) wide. To install the counter into  
the panel cutout, remove the clips from the side of the meter. Slide the meter  
through the panel cutout, then slide the mounting clips back on the meter.  
Press evenly to ensure a proper fit.  
The display refresh, frsh, will slow the numbers of updates to the display. This  
setting ranges from as fast as 480 updates per minute (8 updates per second)  
to as slow as 1 update per minute.  
6
19  
3.2  
Engineering Label Placement  
9.  
MENU DETAIL  
If the engineering unit label needs replacing, place the tip of a ballpoint pen  
into the small hole at the base of the engineering label in the bezel. Slide the  
label up until it pops out. Grasp and remove. Slide the new label half the dis-  
tance in, then use the ballpoint pen to slide it down into place.  
9.1  
Relay Control (Sp1-Sp4)  
While in menu, all other operations are suspended.  
The H340 has four setpoint parameters and up to four relays associated with  
those four setpoints. The setpoint LEDs on the display will light even if no relay  
is present for that setpoint.  
4.  
REMOVING / INSTALLING OPTION MODULES  
To change the setpoint value, enter the menu by pressing W. If the password  
allows relay control, it will be the first menu to appear. The display will show the  
RESET  
ENTER  
word “Sp1”. If this is the setpoint to be edited, press , otherwise press T  
!
to move to the next choice. When editing Sp1, the display will alternate be-  
tween Val-1 and a value. The “value” represents a threshold above or below  
the setpoint being set to alarm.  
Shut off power before removing or installing any option module.  
NOTE: Before editing this value, be sure that the decimal point is in the proper  
position. It is also recommended that any scaling or linearization be entered  
before setpoints are determined.  
1. Remove module from case by inserting a screwdriver into tab slot open-  
ing at top of input module (see Figure 5-1). Apply pressure to release  
module from case. Repeat procedure for tab located on underside of  
module and then slide module away from case.  
RESET  
Press Rto choose Val-1 as the setting to be edited. Notice that the far right  
ENTER  
digit has an alternating cursor. To change this digit, use S or T. To move to the  
next digit, press W. When all changes to the value are complete, press  
RESET  
ENTER  
to confirm the change and save it to memory.  
2. Refer to appropriate sections to configure switches or jumpers for proper  
operation.  
NOTE: Any power loss before confirming a change will lose the edited value.  
The menu will revert back to alternating between Val-1 and value. Press T to  
move to the response setting.  
9.1.1 Response  
RESET  
ENTER  
The display will now show “Rsp.” To edit response, press , otherwise  
press T to move to the next choice. When editing Rsp., the display will show  
Hyst, Dlay, or Ltch Flashing. Use S or T to choose the required response.  
Figure 5-1. Removing Option  
Module  
RESET  
Press  
to confirm the choice. When choosing Hyst, the display will  
ENTER  
alternate between Hyst and the current value.  
RESET  
To edit the value, press ENTER . Otherwise press T to move to the next choice.  
Hysteresis will be used above and below the setpoint in equal amounts. The  
value represents a percentage of the setpoint. For example: If the setpoint is  
set to 100.00 with a high alarm and therhysteresis is set for 8.5%, the alarm  
will not turn on until the reading on the display reaches 108.50. Once tripped,  
the alarm will not turn off until the display reaches 91.50.  
3. Install module by carefully aligning module edges with slots in case and  
pressing forward until tabs (on top and bottom) engage.  
9.1.2 Delay  
When choosing Dlay, the display will alternate between Dlay and current value.  
To edit the value press . Otherwise press q to move to the next choice.  
RESET  
ENTER  
Dlay will be used above and below the setpoint in equal amounts. The value  
represents the amount of delay in seconds. For example, if the setpoint is  
again configured for high alarm and Dlay is set for 2.5 seconds the display  
crosses the setpoint value and a timer begins to count off the 2.5 seconds  
before the alarm trips. If, during those 2.5 seconds the value falls below the  
setpoint, no action will be taken. When the unit successfully counts off 2.5  
18  
7
5.  
OPERATING THE KEYS  
5.1  
In Run Mode  
W = Enters the Program Menu  
S = Displays the Maximum Value (if enabled). Press S and hold while pressing  
RESET  
ENTER  
to clear max. value.  
T= Displays Minimum Value, if enabled. PressTand hold while pressing to  
clear min. value  
RESET  
Page  
2
RESET
= Resets Latched Relays (If any)  
ENTER  
S and T = Sets Zero/ICE Value (if enabled). Also clears Minimum and Maxi-  
mum Values  
ICE  
ZERO  
On  
Off  
Meas  
On  
Off  
5.2  
5.3  
In Program Mode  
HILO  
W = Enters the Edit Mode. Flashing cursor shows value to edit. (Numeric Val-  
ues only)  
OCTL  
S = Scrolls “UP” through menu choices  
T = Scrolls “DOWN” through menu choices  
RESET  
= Selects a menu or submenu to edit.  
ENTER  
RESET  
ENTER  
In Edit Mode  
Frd  
Brd  
Off  
Anlg  
Dir  
W = Moves Edit Cursor to the left. Flashing cursor shows value to edit (Nu-  
meric Values Only)  
SpAn  
HI  
Value  
Value  
S = Increases Numeric Value or Scrolls “UP” through sub-menu choices.  
T = Decreases Numeric Value or Scrolls “DOWN” through sub-menu choices.  
LO  
RESET  
R= Confirms and Saves your new setting.  
ENTER  
Full  
rEAd  
FS  
IMPORTANT: After editing parameters, exit programming menu completely. If  
this step is not followed, changes will not be saved.  
SCTL  
FACt  
rSEt  
Entr  
Pwrd  
PASS  
Cng  
Pwrd  
rst  
Pwrd  
8
17  
8.  
MENU FLOWCHART  
6.  
PROGRAMMING MENU  
Depending on the operator’s password rights, some choices shown below be  
unavailable. Use caution when changing values “on the fly” because relay  
changes are immediate upon exiting menus. While in local menu, RS-485  
communications will halt to avoid command conflict. While in local or remote  
menu, relay and alarm operation are suspended. The local or remote menu  
will “time out” in two minutes and resume normal operation.  
Menu Mode  
Value  
SP1  
SP2  
SP3  
VAL1  
RSP1  
ALR1  
ST1  
HYST  
DLAY  
LTCH  
Value  
6.1  
Relay Control  
HI  
LO  
OFF  
SP1 Set Point #1 & Relay #1 (if present)  
Value 10000*  
Val-1  
ND  
NE  
Hyst  
0* to 29.9%  
Rsp1 (Response 1)  
Value  
VAL2  
RSP2  
ALR2  
ST2  
Dlay* 0* to 60.00 Seconds (0.10*)  
HYST  
DLAY  
LTCH  
Value  
Ltch  
Active  
HI*  
Alr-1 (Alarm 1)  
HI  
LO  
OFF  
LO  
OFF  
ND  
NE  
ND*  
NE  
NE  
De-energized  
Energized or  
De-energized  
St-1 (State when not in Alarm)  
Value  
VAL3  
RSP3  
ALR3  
ST3  
HYST  
DLAY  
LTCH  
Value  
HI  
LO  
OFF  
SP2 Set Point #2 & Relay #2 (if present)  
Value  
Hyst  
Val-2  
ND  
NE  
0* to 29.9%  
Rsp2 (Response 2)  
Dlay* 0* to 60.00 Seconds (0.10*)  
Value  
SP4  
VAL4  
RSP4  
ALR4  
ST4  
Ltch  
Active  
HYST  
DLAY  
LTCH  
Value  
HI*  
LO  
OFF  
Alr-2 (Alarm 2)  
HI  
LO  
OFF  
ND*  
NE  
St-2 (State when not in Alarm)  
ND  
NE  
DCTL  
Deg  
C
F
SP3 Set Point #3 & Relay #3 (if present)  
Frsh  
Value  
Value  
Value  
Val-3  
Band  
Brit  
Hyst  
0* to 29.9%  
Rsp3 (Response 3)  
Dlay* 0* to 60.00 Seconds (0.10*)  
Value  
Page  
2
Ltch  
Active  
HI  
Alr-3 (Alarm 2)  
LO  
Off*  
ND*  
NE  
St-3 (State when not in Alarm)  
*Factory Reset Default Values  
16  
9
The hold feature is used to freeze the display. When the contacts are shorted,  
the display will “Hold” the last reading until the short is removed. It is recom-  
mended that a mechanical switch or relay be used to activate the hold circuit,  
solid state relays may give unexpected results. The hold circuit cannot be ex-  
ternally powered.  
SP4 Set Point #4 & Relay #4 (if present)  
Value 10000*  
Hyst 0* to 29.9%  
Dlay* 0* to 60.00 Seconds (0.10*)  
Val-4  
Rsp4 (Response 4)  
Ltch  
Active  
!
HI*  
LO  
OFF  
Alr-3 (Alarm 4)  
No terminal can be above earth ground by more than 250Vrms. An external  
fuse is recommended for safe operation, for AC supply, Slow Blow fuse at  
.25A, Littlefuse Part No. 313.250 or equal. For DC supply Slow Blow fuse at  
1.25A, Littlefuse Part No. 3131.25 or equal.  
ND*  
NE  
St-4 (State when not in Alarm)  
*Factory Reset Default Values  
6.2  
Display Control  
!
Hazardous voltages may be present. Disconnect power before making or re-  
moving connections.  
DctL  
C*(Celsius) F (Fahrenheit) Fixed based on  
RTD or TC  
deg(rees)  
Value - 1 to 480 updates per minute (240*)  
Value - 0* to 99 counts from current value.  
Frsh (Refresh)  
Band  
S and T arrows move LED brightness  
through 5 levels as indicated on display.  
(5* full brightness)  
Brit (Brightness)  
*Factory Reset Default Values  
6.3  
Measurement Control  
MEAS  
Off*  
(Zero)  
On - Temporary TC Correction  
(Until power cycle)  
ICE (Point)  
Hold - Permanent TC Correction  
Off*  
On  
HILO (Minimum/Maximum)  
Display Enable  
10  
15  
The relay cards are directly related to any alarms that occur on the Hawk 3.  
The single relay is a “Form C” relay that activates in relationship to “SP1”.  
The dual relay is a Form C” relay that activates in relationship to “SP1” &  
“SP2”.  
The quad relay is a “Form A” relay that activates in relationship to “SP1” through  
“SP4”.  
6.4  
Output Control (If Present)  
OctL  
ALog out  
LIM  
HI (electrical limit)  
(100*)  
Lo (electrical limit)  
(0*)  
NOTE: “SP3” and “SP4” connections share a common.  
FS (Fail safe)  
HI (move to 20mA)  
(Overrange or Underrange LO (move to 4mA)  
Off*  
!
All relay contacts are rated at 250VAC @ 5 amp maximum. The rating of the  
relay contact is intended for resistive circuits only. Use a snubber circuit to  
protect the contacts from inductive loads.  
6.5  
System Control  
(The process meter will have pre-loaded coordinates)  
7.2  
Frequently Asked Questions  
SctL  
What is a Form A or Form C relay?  
Reset (Selecting this item will reset the  
device to default values and return to  
menu)  
FACT/rSET (Factory  
Reset)  
The form A relay is a 1 contact switch that is either closed or open. The form C  
relay has 2 contacts, one of which will be closed and one open. With the fac-  
tory defaults used, N.O. on the relay means normally open when the Hawk 3 is  
not in alarm. N.C. means normally closed when the Hawk 3 is not in alarm.  
What does N.D. and N.E. do to the relay?  
The effect of the relay can be reversed by setting the relay action to N.E. (nor-  
mally energized) in the menu. When the Hawk 3 is not in alarm, the N.C.  
contact will now be open and the N.O contact will be closed. Setting the alarm  
response back to N.D. (normally de-energized) will put the contacts back to  
their default state.  
7.3  
Power Supply Card  
3-1/2 Digit 120 VAC Supply  
Universal AC Supply  
DC to DC Supply  
IN  
IN  
+
~
~
IN  
IN  
~
~
9-36VDC  
85-250VAC  
50/60 Hz  
10VA  
85 - 250 VAC  
50/60 Hz  
10VA  
10W  
HOLD  
HOLD  
HOLD  
The AC power cards are meant to operate from standard 50/60 Hz line power.  
The DC to DC power card is an isolated supply that can operate between 9  
and 32 volts DC.  
14  
11  
6.6  
Password  
7.  
TEMPERATURE INPUT CARDS  
RTD PT100: The resistance input card has been configured  
to track the characteristics of a PT100 sensor.  
Pass (Password)  
RTD  
PT100  
000*  
Full Access.  
Lead length error can be cancelled out by bringing the sensor  
to 0 C (ice point) and using the “ICE” command to zero the  
meter. (Remember to move the ICE capture from the “On” to  
“Hold” in order to retain the data.)  
001 to 200  
201 to 400  
No access to scale or factory reset.  
No access to scale, factory reset or  
measurement control.  
IN HI  
Lead length error can also be cancelled using the guard wire.  
SENSE  
401 to 600  
601 to 800  
No access to scale, factory reset,  
measurement control or output control.  
IN LO  
TEMPERATURE  
No access to scale, factory reset,  
measurement control, output control or relay  
control.  
7.2 J, K, E, T Thermocouple: The thermocouple input card  
contains all the response information needed to read a J  
type or K type thermocouple.  
801 to 999  
-999  
No access except password entry  
THERMO  
Keypad lockout. All future key strokes will be  
ignored. All setting changes must come from  
RS-485 port. This choice is available only if  
the RS-485 card is present and configured  
for "Full".  
COUPLE  
J,K,E,T  
Lead length error can be cancelled out by bringing the cen-  
sor to 0 C (ice point) and using the “ICE” command to zero  
the meter. (Remember to move the ICE capture from “On” to  
“Hold” to retain the data.  
IN+  
IN--  
CHG  
Change the password to a new value. This is  
available only after successfully entering the  
current password or if the password is set to  
000.  
Nu-pas  
(New  
Password)  
!
TEMPERATURE  
Never apply a voltage or current to these inputs as damage  
will occur.  
NOTE: If you forget your password, turn power off in unit, press and hold the  
key and the key. Turn power on and wait until the display reads “noPas”  
RESET  
ENTER  
RESET  
ENTER  
7.1  
Relay Cards  
T
then press the r
key again to reset password to 000.  
Single Relay  
Quad Relay  
Dual Relay  
* Factory Reset default value  
N.O.  
1
N.C.  
N.C.  
COM  
1
COM  
N.O.  
1
COM  
N.O.  
N.O.  
2
COM  
250V~  
N.C.  
5A  
250V~  
5A  
N.O.  
3
COM  
4
2
COM  
N.O.  
N.O.  
RELAY OUT  
RELAY OUT  
RELAY OUT  
250V  
5A  
12  
13  

Toshiba MQ01ABD Series Hard Disk Drive MQ01ABD025 User Manual
Toastmaster TCM8TD User Manual
Sony DREAM MACHINE ICF C414 User Manual
SIIG 04 0205F User Manual
Seagate MOMENTUS ST9250410ASG User Manual
Samsung TS HB33 User Manual
Samsung GH68 18086A User Manual
PYLE Audio PYLE Plus Series PLCD10CH User Manual
Parrot Cell Phone CK3000 User Manual
Numark Industries MX25 User Manual