Tripp Lite Power Supply 93 2120_ES User Manual

Owner’s Manual  
PDU Rackmount Power Strips  
Designed for Mounting in 19 in. Racks  
Español: p. 3 • Français: p. 5  
IMPORTANT SAFETY INSTRUCTIONS. This manual contains information  
concerning the proper installation and use ofTripp Lite’s Rackmount Power Strips.  
SAVE THESE INSTRUCTIONS.  
Do not connect your power strip to an ungrounded outlet. Do not use it with extension cords  
or adapters that eliminate its connection to ground. Your power strip is designed for indoor  
use only. Install it away from heat emitting devices such as radiators and heat registers. Do  
not install where excessive moisture or other conductive contaminants are present. Never  
install electrical wiring during a lightning storm.  
The power requirement of each device connected to an outlet of your power strip must not  
exceed the Outlet Power Rating of your power strip (see Specifications). The total power  
requirements of all devices connected to your power strip must not exceed the Maximum  
Load Rating of your power strip (see Specifications).  
1U Rackmount Installation  
To Mount Unit in Rack: Put four user-supplied rackmount  
screws (A) through the unit’s mounting ears (B) and into the  
rack rails as shown. The user must determine the fitness of the  
rackmount screws to hold the unit in the rack before  
installation.  
0U Rackmount Installation  
1. Reorient Mounting Ears: Unscrew the screws (A) holding  
the unit’s mounting ears (B) to the sides of the unit. Use  
the screws from Step 1 (A) to reattach the mounting ears  
1U Rackmount Installation  
(B) to the unit as shown. Use only the manufacturer-  
supplied screws or their equivalent (#6-32, ¼" flat head)  
to reattach the mounting ears.  
2. Mount Unit on Outside of Rack Rails: Put four user-  
supplied screws (C) or similar mounting hardware  
through the unit’s mounting ears (B) and into the side of  
the rack as shown. The user must determine the fitness of  
the user-supplied mounting hardware to support the unit  
before mounting.  
Wallmount/Under Counter Installation  
Reorient the unit’s mounting ears as per the 0U Rackmount  
Installation above, then put four user-supplied screws or  
similar mounting hardware through the unit’s mounting ears  
and into the mounting surface. The user must determine the  
fitness of the user-supplied mounting hardware to support  
the unit before mounting.  
0U Rackmount Installation  
 
Features  
Circuit Breaker(s)  
If the current draw of the equipment connected to your power strip exceeds your model’s Maximum Load  
Rating (see Specifications) for longer than a few seconds, a circuit breaker will trip to prevent any possible  
damage. When a circuit breaker trips, its plunger will pop up. Remove excess equipment and allow the breaker  
to cool one minute before depressing its plunger to reset the breaker.  
Grounding Lug  
Use this screw (located by the power strip’s receptacles) to connect your power strip to ground.  
Input Receptacle (IEC Model Only)  
The PDU12IEC has no power cord. Instead, it has a IEC320-C20 inlet receptacle. To connect a PDU12IEC  
to utility power, use a user-supplied detachable power cord with an IEC plug on one end and a plug  
appropriate to your local utility outlets on the other.  
Specifications  
PDU1215  
PDU1220  
PDU2430  
Nominal Voltage/Frequency:  
Output Power Rating (amps):  
AC Receptacles:  
120V/50 or 60 Hz  
15 amps  
13 x NEMA 5-15R  
(12 rear/1 front)  
120V/50 or 60 Hz  
20 amps  
13 x NEMA 5-15/20R  
(12 rear/1 front)  
120V/50 or 60 Hz  
24 amps  
24 x NEMA 5-15R  
(12 rear/12 front)  
AC Line Cord:  
15', w/NEMA 5-15P plug  
15 amps  
1¾ × 17¼ × 3¾  
UR, cUR  
15', w/NEMA 5-20P plug 15', w/NEMA L5-30P plug  
Circuit Breaker(s) (Resettable):  
Dimensions (HxWxD, inches):  
Approvals:  
20 amps  
2 x 15 amps  
1¾ × 17¼ × 3¾  
UL, cUL  
1¾ × 17¼ × 3¾  
UR, cUR  
PDU12IEC  
PDU1220T  
Nominal Voltage/Frequency:  
Output Power Rating (amps):  
100V to 240V/50 or 60Hz  
15 amps for 100V to 120V or  
16 amps for 208 to 240V  
120V/50 or 60 Hz  
20 amps  
AC Receptacles:  
4 x IEC-C13 (front),  
13 x NEMA 5-15/20R  
(12 rear/1 front)  
15', w NEMA L5-20P plug  
20 amps  
1¾ × 17¼ × 3¾  
UR, cUR  
8 x IEC-C13/2 x IEC-C19 (rear)  
N/A (IEC320-C20 inlet)  
2 x 16 amps  
1¾ × 17¼ × 3¾  
CE, UL, cUL  
AC Line Cord:  
Circuit Breaker(s) (Resettable):  
Dimensions (HxWxD, inches):  
Approvals:  
Limited Lifetime Warranty  
Seller warrants this product, if used in accordance with all applicable instructions, to be free from original defects in material and  
workmanship for its lifetime. If the product should prove defective in material or workmanship within that period, Seller will repair or  
replace the product, in its sole discretion. Service under this Warranty can only be obtained by your delivering or shipping the product  
(with all shipping or delivery charges prepaid) to: Tripp Lite, 1111 W. 35th Street, Chicago, IL 60609. Seller will pay return shipping  
charges. Call Tripp Lite at (773) 869-1234 before sending any equipment back for repair.  
THIS WARRANTY DOES NOT APPLY TO NORMAL WEAR OR TO DAMAGE RESULTING FROM ACCIDENT, MISUSE, ABUSE OR  
NEGLECT. SELLER MAKES NO EXPRESS WARRANTIES OTHER THAN THE WARRANTY EXPRESSLY SET FORTH HEREIN.  
EXCEPT TO THE EXTEND PROHIBITED BY APPLICABLE LAW, ALL IMPLIED WARRANTIES, INCLUDING ALL  
WARRANTIES OF MERCHANTABILITY OR FITNESS, ARE LIMITED IN DURATION TO THE WARRANTY PERIOD SET FORTH  
ABOVE; AND THIS WARRANTY EXPRESSLY EXCLUDES ALL INCIDENTAL AND CONSEQUENTIAL DAMAGES. (Some states  
do not allow limitations on how long an implied warranty lasts, and some states do not allow the exclusion or limitation of incidental  
or consequential damages, so the above limitations or exclusions may not apply to you. This Warranty gives you specific legal rights,  
and you may have other rights which vary from jurisdiction to jurisdiction).  
WARNING: The individual user should take care to determine prior to use whether this device is suitable, adequate or safe  
for the use intended. Since individual applications are subject to great variation, the manufacturer makes no  
representation or warranty as to the suitability or fitness of these devices for any specific application.  
Policy of Tripp Lite is one of continuous improvement. Specifications are subject to change without notice.  
 
2

Telenetics Network Card DSP 9612 User Manual
Telex Marine Radio ur 700 User Manual
TRENDnet Security Camera TVIP322P User Manual
Tripp Lite Power Supply APSINT Series User Manual
Ultra Start Automobile Electronics Key 5 User Manual
Vantec Computer Drive LX ULTRA User Manual
Vax Vacuum Cleaner C91 P2 User Manual
Viking Telescope PC 7 User Manual
VTech Telephone VT1121 User Manual
Vulcan Hart Convection Oven E14 User Manual